<br />SERVICE EQUIPMENT NOTES: <br /> <br />1. SERVICE EQUIPMENT SHAll HAVE A SHORT CIRCUIT TO <br />WITHSTAND RATING THAT IS EQUAL TO OR EXCEEDS THE <br />MAXIMUM AVAilABLE FAULT CURRENT AT THE SUPPLY <br />TERMINAl. THE INSTAlLATION SHAll BE FREE FROM ANY <br />SHORT CIRCUITS AND GROUNDS. <br />2. ALL ELECTRICAl EQUIPMENT SHAll BE ANCHORED TO <br />WITHSTAND 80 M.P.H. WIND SPEED, EXPOSURE C. <br />3. ALL ELECTRICAL EQUIPMENT SHALL BE lABELED WITH <br />PERMANENT ENGRAVED PLASTIC LABELS. <br />4_ PATCH, REPAIR AND PAINT ANY AREA THAT HAS BEEN <br />DAMAGED IN THE COURSE OF ELECTRICAL WORK. <br /> <br />CONDUCTOR NOTES: <br /> <br />1. All CONDUCTORS SHAll BE COPPER <br />2_ All WIRING SHAll BE COPPER WITH <br />THHN/THWN DUAl MIED 600 VOLTS INSULATION. <br />3. CONDUCTORS SHAll BE 12 AWG MINIMUM <br />UNLESS $PECIF1CAll Y NOTED OTHERWISE <br />4. GROUNDING CONDUCTORS SHALL BE SOUD <br />TINNED COPPER UNLESS OTHERWISE NOTED. <br /> <br />UTILITY COORDINATION NOTES: <br /> <br />1. PROVIDE POWER AND TelEPHONE TO SERVICE POINTS PER <br />UTIliTY COMPANY REQUIREMENTS. CONTRACTOR SHALL <br />CONTACT UTILITY SERVICE PLANNERS AND OBTAIN All SERVICE <br />REQUlREMENTS AND INCLUDE COSTS FOR SUCH IN HIS 810. <br />2. CONTRACTOR TO COORDINATE WITH UTILITY COMPANY FOR <br />CONNECTION OF TEMPORARY AND PERMANENT POWER TO HE <br />SITE. THE TEMPORARY POWER AND All HOOKUP COSTS TO BE <br />PAID BY CONTRACTOR. <br />3, PROVIDE DAILY UPDATES TO PM UNTIL FINAL elECTRICAL <br />SERVICE IS EFFECTED. <br /> <br />NOTE: <br /> <br />GC TO INSTALL NEW 30 AMP DfSCONNECT <br />BREAKER INSIDE PPC CABINET AND LABEL (UMTS) <br /> <br />;:r- . . Mobile. <br /> <br />T-MOBllE <br />8550 WEST BRYN MAWR AVE. <br />SUITE 100 <br />CH!CAGO,ll60631 <br />MAIN: (773) 444-5400 <br /> <br />CONDUIT NOTES: <br /> <br />NOTES: <br /> <br />CONCORDIA, LTD <br />A PROFE.SS!O~ DESIGNf!RM <br />~ llCENSE#184.004952.D.BA <br />_ ~~CORDlA WIRELESS, INC. <br />- - 505 E. GOLF ROAD <br />SUITED&E <br />ARLINGTON HEIGHTS,Il60005 <br />MAIN: {847) 981-0801 <br /> <br />1. HWGC SHAll BE USED WHEN INSTALLED INOR <br />UNDER CONCRETE SLABS, IN CONTACT WITH EARTH, <br />OR EXPOSED ABOVE GRADE. <br />Z. EMT SHALL BE USED ONlY FOR !NTERIORS RUNS <br />AND SHALL HAVE COMPRESSION TYPE FIDINGS. <br />3. SEAL TIGHT, FLEXlBlECONDUITMAYBEUSED <br />WHERE CODE PERMITS. ALL CONDUIT SHALL HAVE <br />FUlL SIZE EQUIPMENT GROUND WIRE. <br />4. PVC SHAll BE SCH 40 <br />5. SERVICE CONDUITS SHALL HAVE NO MORE THAN (3) <br />-90' BENDS !N ANY SINGLE RUN. THE CONTRACTOR <br />SHALL PROV!OE PULL BOXES AS NEEDEO WHERE <br />CONDUIT REQUIREMENTS EXCEED THESE <br />CONDlTJON$. <br />6. SERVICE CONDun SHAlL BE AT A MINIMUM DEPTH <br />OF4Z". <br />7. AlL COtv<, POWER AND TELEPHONE SYSTEM <br />CONDUIT SHALL HAVE A MIN!MUM 24" RADIUS SWEEPS <br />TO EQUIPMENT, PUlL80XE$, MONOPOLE, ETC., <br />UNLESS OTHERWISE NOTED, OR AS REQUIRED BY <br />unllTY COMPANIES. <br /> <br />n IT SHALL BE THE CONTRACTOR'S RESPONSIB!lITY TO <br />COORDINATE W!TH THE PROPERTY OWNER & NECESSARY <br />UTILITY COMPANIES FOR THE LOCATION OF All EXISTING <br />BELOW GRADE UTILITIES PRIOR TO BEGINNING CONSTRUCTION <br />SHAll BE RESPONSIBLE FOR ANY DAMAGE COSTS <br />ASSOCIATED WITH EXISTING BELOW GRADE UTILITIES. <br />2.} CONTRACTOR TO COORDINATE WITH UTILITY COMPANY FOR <br />CONNECTION OF TEMPORARY AND PERMANENT POWER TO <br />THE SITE. THE TEMPORARY POWER AND ALL HOOKUP COSTS <br />TO BE PAID BY CONTRACTOR. <br />3.) CONTRACTOR TO VERIFY LOCAL UTILITY REQUIREMENTS <br />FOR DEPTH, SIZE & SEPARAT!ON OF CONDUIT PRIOR TO <br />INSTAllATION. NOTIFY CONSTRUCTION MANAGER <br />IMMEDIATELY OF ANY DISCREPANCIES <br />4.) CONTRACTOR TO CAll J_U.LIE (800) 892-0123 48 HRS. <br />PRIOR TO EXCAVATING FOR UNDERGROUND UTILITY <br />lOCATIONS. SURROUNDING EXCAVATED AREA MUST BE <br />PRIVATELY LOCATED FOR NONPUBUC UTIlIT!ES. <br /> <br />(qConCOfdiaW01-Z009,CopyrightNotlco: <br />Thes<> OocumentslOrnwings Aro ProduC<l<l by and <br />Are Thereforo The Int'llloctualPropertyof <br />Concordia Group Of Companies. Do NotCopy, <br />Reproduce, Reverse-EnglnOOl"orRepUcateArly <br />Parts of Those Doeuments In any Manner Wlthoul <br />Obta'n;ngWrltlen ConsenlfromTheConeoro!a <br />Group, <br /> <br />DRAWN BY; KF CHECKED BY: OMS <br /> <br />CHECKED BY, RH APPROVED BY: OMS. TP <br /> <br />NOTES: <br /> <br />CONDUIT MATERIAL SCHEDULE: <br /> <br />1. ALL CONDUITS & CONDUCTORS FURNISHED AND <br />INSTALLED BY CONTRACTOR UNLESS NOTED <br />OTHERWISE. <br />2. SEE SINGLE-LINE DIAGRAM FOR UTILITY CONDUITS <br />& CONDUCTOR SIZES. <br />3. ALL UTILITY LOCATIONS AND CONNECTIONS TO BE <br />VERIFIED WITH T-MOBILE REPRESENTATIVE, <br />4. BEllOW GRADE CONDUITS FROM PPe-CABINET TO <br />BE RGS FROM ELBOW TO STUB-UP. <br /> <br />UNLESS NOTED OTHERWISE, All CONDUIT RUNS SHALL <br />CONFORM TO THE FOLLOWING: <br />1.) All ABOVE GRADE, EXTERIOR CONDUITS SHAll BE RGS_ <br />2.}AllBELOW GRADE HORIZONTAL CONDUITS SHALL BE PVC <br />3.)AlL BELOW GRADE 3>> 0 & 45" BENDS SHALL BE PVC <br />WffHREADED CONNECTIONS. <br />4.) ALL BelOW GRADE TO ABOVE GRADE R!SERS SHALL BE <br />PVC WffHREADED CONNECTIONS. <br />5.) SEAL TIGHT FLEXIBLE CONDUIT MAY BE USED WHERE CODE <br />PERMITS. <br /> <br />NOTES ON TELCO & POWER COORDINATION <br /> <br />ATTENTION GC: <br /> <br />ROUTING SHOWN IS BASED ON ASSUMPTIONS FROM <br />VISUAL FIELD OBSERVATIONS OF EXISTING POLES & <br />TRANSFORMERS. IF THESE PLANS REFlECTfCONTAIN <br />MULTIPLE POWERrTELCO ROUTING SCENARIOS <br />GC SHALL8E RESPONSIBLE FOR VERIFYING FINAL <br />SCENARIO. COORDINATION BY T-MOBllE. GC SHAll BID <br />ON THESE PLANS USING THE WORST CASE SCENARIO. <br /> <br />1.) CONTRACTOR TO COORDINATE WITH UTILITY COMPANY FOR <br />CONNECTION OF TEMPORARY AND PERMANENT POWER TO <br />THE SITE. THE TEMPORARY POWER AND ALL HOOKUP COSTS <br />TO BE PAID BY CONTRACTOR. <br />2.) CONTRACTOR TO VERIFY LOCAL UTIUTY REQUIREMENTS <br />FOR DEPTH, TYPE, SIZE & SEPARATION OF CONDUIT PRIOR TO <br />INSTALLATION. NOTIFY CONSTRUCTION MANAGER <br />IMMEDIA TEL Y OF ANY DISCREPANCIES <br />3.) CONTRACTOR TO CALL UTILITY lOCATE HOTLINE 48 HRS. <br />PRIOR TO EXCAVATING FOR UNDERGROUND UTILITY <br />LOCATIONS. SURROUNDING EXCAVATED AREA MUST BE <br />PRIVATElY LOCATED FOR NONPUBlIC UTILITIES. <br />4,) ALL ABOVE GRADE OR WEATHER EXPOSED CONDUITS <br />SHAll BE OF RIGID GALVANIZED CONDUIT! <br /> <br />ELECTRICAL NOTES <br /> <br />E-2 <br />