Laserfiche WebLink
. . <br /> OIL TESTINGr <br /> Dielectric Strength ASTM 0.877 � <br /> The most critical test of insulating oil is <br /> the dielectric strength,because it tells <br /> if the oil is capable of providing the °:::F. <br /> electrical insulation required.The test y"` --- <br /> result is the voltage at which the oil <br /> breaks down and allows an electrical <br /> ilk <br /> arc to pass between two electrodes.A <br /> poor dielectric test(25 KV or less,21 KV <br /> the minimum)would indicate a high <br /> presence of contaminates such as <br /> water,carbon or dirt particles. <br /> Color ASTM D-1500 <br /> This test is a comparison of the color of :Alio <br /> a sample to a chemical standard. New , ,,I "• a <br /> Oil will have a color number of.5 or less. � ' <br /> A number of 4.0 would be considered to a <br /> ;' ) t <br /> be unacceptably high for transformer oil r <br /> with a naphthenic base.Parafenic t'al" <br /> based oil will be darker. <br /> ; ' .....4 ;#110,,i''' <br /> Acidity ASTM D•974 <br /> The acid content of insulating oil is a -T <br /> measure of its deterioration and of its '.4 ,r�'�'' o< <br /> tendency to form sludge.The term N 1,. <br /> neutralization number is employed to ,..,-: : u _iii.„,,,. <br /> express the acidity of the oil. It is the �� <br /> quantity of potassium hydroxide(KOH) -----�'- ,.4..'�x <br /> in milligrams needed to neutralize one s , <br /> gram of insulating fluid.A .- <br /> recommended minimum neutralization <br /> number for new transformer oil is less <br /> than 0.1. (i.e. 0.1 mg KOH/g.) 4 <br /> Interfacial Tension ASTM D:971 '`� .-4 z <br /> This test is a measure of strength of the <br /> surface film of the oil in contact with <br /> water.The test is performed on an <br /> Interfacial Tensiometer. This test <br /> measures polar contaminants in the oil, <br /> giving an overall indication of changes in AteAllH .- , <br /> the insulating oil without being selective <br /> as to the cause. New oil may have an _ <br /> interfacial tension as high as 50 dynes �4's <br /> per centimer, while badly aged oil may ; <br /> be below 15 dynes per centimeter. ...•,... <br /> Gas Chromatography ----- --- <br /> Deterioration of a transformer -- <br /> insulation system will cause certain 3 - <br /> n 1 _x ;, <br /> I <br /> combustible gases to form.It is . y : ■ . <br /> estimated that 25% of transformers in �'t i �, �I- g lk �,, <br /> use have combustible gases being _ ° °t �� • ••generated.Various conditions of 1 .,,; p: a v,'• •• <br /> transformer heating or arcing will <br /> generate acetylene,hydrogen,methane, i - ''l .:. I <br /> ethane and ethylene.t Heating of _m.= <br /> cellulose present in transformers will - <br /> produce carbon monoxide. <br /> Detection of these gases,the <br /> identification and rate of generation can ® _ <br /> be helpful in determining the health of a // <br /> transformer.The gases are extracted <br /> from the oil or head space and then <br /> analyzed by our chemist using a gas • <br /> chromatograph. <br />