CZARNECKI <br /> ENGINEERING <br /> INCORPORATED <br /> 1 121 MARLIN COURT • SUITE B • WAUKESHA, WI 53186 <br /> 262.513.2020 FAX 262.513.2023 www.czeng.com <br /> August 24, 2016 <br /> Dawn O'Kroley <br /> Dorschner Associates <br /> Via email <br /> RE: Blooming Grove Fire Department <br /> 1880 South Stoughton Road <br /> Blooming Grove, WI <br /> Dear Dawn, <br /> I visited the site with you on August 16, 2016 to review the existing electrical system. The <br /> following are my findings: <br /> ELECTRIC SERVICE <br /> The building is served underground from a pole mounted transformer near the northwest corner <br /> of the building. Service terminates on an exterior current transformer cabinet near the center of <br /> the building. Service is 208Y/120 volts, 3phase, 4 wire with a capacity of 400 amperes. Service <br /> terminates in a pair of panelboards on the west wall of the garage. These are Cutler Hammer <br /> type PRL1A. One contains a 400 amp 3 pole main breaker; the second panel is sub fed from <br /> the first. The panels are in good condition. The area around them is clean. There is room for <br /> additional electrical equipment at these panels. The service does not have surge protection. <br /> There is room for additional circuit breakers in the panels. A 100 amp flush mounted Cutler <br /> Hammer load center in the office area is fed from the panels in the garage. <br /> This service is adequate for the proposed project. <br /> One panel in the office area is impacted by the proposed remodeling and will need to be moved. <br /> ELECTRICAL DISTRIBUTION <br /> There is an adequate amount of receptacles in the facility. The building was built in 2010 so the <br /> electrical system is relatively new. The building appears to be wired with a combination of <br /> electrical metallic tubing and MC cable. <br /> LIGHTING <br /> The existing lighting is fluorescent with T8 lamps. Fixtures in the office area are recessed lay-in <br /> type with prismatic acrylic lenses. Fixtures in the garage are pendant industrial type. Some <br /> areas are controlled by occupancy sensor type wall switches. Some areas have dual switching. <br /> The fixtures are in reasonably good condition and can be reused. <br /> EMERGENCY LIGHTING <br /> The building does not have a generator. Selected fluorescent fixtures have internal battery <br /> backup. The exit lights also have battery backup. There are no emergency fixtures on the <br /> outside of the building. <br />